Language: English

You are here:        Home > Product > DIN-RAIL series > MDR series >

recommended

40W Din-rail Power Supply

  • Product Overview
  • Send Inquiry
  • 1.Features

    •Universal AC input/Full range
    •Protections: Short circuit / Overload / Over voltage
    •Cooling by free air convection
    •Can be installed on DIN rail TS-35/7.5 or 15
    •Built in DC OK active signal
    •LED indicator for power on
    •No load power consumption<0.75W
    •100% full load burn-in test
    •2 years warranty

    2. Specification

    MODEL
    MDR-40-5
    MDR-40-12
    MDR-40-15
    M DR-40-24
    MDR-40-48
    OUTPUT
    DC VOLTAGE
    5V
    12V
    15V
    24V
    48V
    RATED CURRENT
    6A
    3.33A
    2.66A
    1.7A
    0.83A
    CURRENT RANGE
    0~6A
    0-3.33A
    0-2.66A
    0 ~ 1.7A
    0 ~ 0.83A
    RATED POWER
    30W
    40W
    39.9W
    40.8W
    39.8W
    RIPPLE & NOISE (max.) Note.2
    80mVp-p
    120mVp-p
    120mVp-p
    150mVp-p
    200mVp-p
    VOLTAGE ADJ. RANGE
    5-6V
    12 ~ 15V
    15-18V
    24 - 30V
    48 - 56V
    VOLTAGE TOLERANCE Note.3
    ±2.0%
    ±1.0%
    ±1.0%
    ± 1.0%
    ± 1.0%
    LINE REGULATION
    ±1.0%
    ±1.0%
    ±1.0%
    ±1.0%
    ±1.0%
    LOAD REGULATION
    ±1.0%
    ±1.0%
    ±1.0%
    ± 1.0%
    ± 1.0%
    SETUP, RISE TIME Note.5
    500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load
    HOLD UPTIME (Typ.)
    50ms/230VAC 20ms/115VAC at full load
     
     
    VOLTAGE RANGE
    85 ~ 264VAC 120 ~ 370VDC
    INPUT
    FREQUENCY RANGE
    47 ~63Hz
    EFFICIENCY (Typ.)
    78%
    86%
    86%
    88%
    88%
    AC CURRENT (Typ.)
    1.1 A/115 VAC 0.7A/230VAC
    INRUSH CURRENT (Typ.)
    COLD START 30A/115VAC,60A/230VAC
    LEAKAGE CURRENT
    <1mA/240VAC
    PROTECTION
    OVERLOAD
    105 ~ 160% rated output power
    Protection type : Constant current limiting, recovers automatically after fault condition is removed
    OVER VOLTAGE
    6.25 - 7.25V
    15.6 -18V
    19.5-22.5V
    31.2-36V
    57.6-64.8V
    Protection type : Shut down o/p voltage, re-power on to recover
    FUNCTION
    DC OK ACTIVE SIGNAL (max.)
    Relay contact rating{max.): 30V/1A resistive
    ENVIRONMENT
    WORKING TEMP.
    -20 ~ +70C (Refer to "Derating Curve")
    WORKING HUMIDITY
    20 ~ 90% RH non-condensing
    STORAGE TEMP., HUMIDITY
    -40 ~ +85C, 10 ~ 95% RH
    TEMP. COEFFICIENT
    ±0.03%/C (0 ~ 50℃)
    VIBRATION
    Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
    SAFETY &EMC      (Note 4)
    WITHSTAND VOLTAGE
    I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
    ISOLATION RESISTANCE
    I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25C/ 70% RH
    EMC EMISSION
    Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
    EMC IMMUNITY
    Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024,EN61000-6-1,EN61204-3, light industry level, criteria A
    OTHERS
    MTBF
    301.7K hrs min. MIL-HDBK-217F (25℃)
    DIMENSION
    40*90*100mm (W*H*D)

    3. Mechanical Dimension

    4. Block Diagram

    5.DC OK Relay Contact

    6Derating Curve

    7.Output Derating VS Input Voltage

    8. Please Note

    1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
    2.Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1 uf & 47uf parallel capacitor.
    3.Tolerance : includes set up tolerance, line regulation and load regulation.
    4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
    5.Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.



  • If you have any enquiry about quotation or cooperation, please feel free to email us at maggie-liu@yqmingwei.com or use the following enquiry form. Our sales representative will contact you within 24 hours. Thank you for your interest in our products.

    E-mail *
      For example : cbh@sscmwl.com
    Message *
    Product
    Your Name *
      For example : Smith Zhang. First name and Last name
    Company
      For example : Yueqing Mingwei Electric Co.,Ltd.
    Country
      For example : China
    Telephone
      For example : 0086-577-62777777 (Country code + City code + Tel numbers)
     

Yueqing Mingwei Electric Co., Ltd.2014 All Rights Reserved    Powered:盛世传媒-温州网站建设-乐清网站建设