DR-75
DR series
- Product Overview
- Send Inquiry
-
1.Features
Universal AC input/ full range Protections: Short circuit/Over load/Over voltage/Over temperature Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 LED indicator for power on 100% full load burn-in test Fixed switching frequency at 50KHz 2 years warranty 2. Specification
ModelDR-75-12DR-75-24DR-75-48OUTPUTDC Voltage12V24V48VRated Current6.3A3.2A1.6ACurrent Range0-6.3A0-3.2A0-1.6ARated Power75.6W76.8W76.8WRipple & Noise (max.) Note.2100mVp-p150mVp-p240mVp-pVoltage Adj. Range12-14V24-28V48-53VVoltage Tolerance Note.3±2%±1%±1%LINE REGULATION±0.5%±0.5%±0.5%LOAD REGULATION±1%±1%±1%Setup, Rise Time1000ms, 60ms/230VAC 1800ms, 60ms/115VAC at full loadHold Up Time60ms/230VAC 12ms/115VAC at full loadINPUTVoltage Range85~264VAC 120~370VDCFREQUENCY RANGE47~63HzAC Current1.6A/115V 0.96A/230VEfficiency76%80%81%Inrush CurrentCOLD START 20A/115VAC 40A/230VACLEAKAGE CURRENT<1mA / 240VACPROTECTIONOver Load105%~150% rated output powerProtection type: Constant current limiting, recovers automatically after fault condition is removedOver Voltage15 ~ 16.5V29 ~ 34V58 ~ 65VProtection type : Shut down o/p voltage, re-power on to recoverOVER TEMPERATURE85°C± 5°C (TSW1) detect on heat sink of power transistorProtection type : Shut down o/p voltage, recovers automatically after temperature goes downENVIRONMENTWorking Temp.,-10°C~+60°C; (Refer to "Derating Curve")WORKING HUMIDITY20 ~ 90% RH non-condensingStorage Temp., Humidity-20°C~+85°C; 10%~95%RHTemp. Coefficient±0.03%/°C(0~50°C)Vibration10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axesSAFETYWithstand VoltageI/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVACIsolation ResistanceI/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25°C / 70% RHEMC EMISSIONCompliance to EN55011, EN55022 (CISPR22) Class B, EN61000-3-2,-3EMC IMMUNITYCompliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria AOTHERSMTBF123.1K hrs min. MIL-HDBK-217F (25°C )DIMENSION55.5*125.2*100mm (W*H*D)3.Mechanical Specification
4.Block Diagram
5.Output Derating O
6.Output Derating Vs Input Voltage
7. Please Note
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
-
If you have any enquiry about quotation or cooperation, please feel free to email us at maggie-liu@yqmingwei.com or use the following enquiry form. Our sales representative will contact you within 24 hours. Thank you for your interest in our products.