Language: English

You are here:        Home > Product > DIN-RAIL series > DR series >

recommended

60W Din-rail Power Supply

  • Product Overview
  • Send Inquiry
  • 1.Features

    Universal AC input/ full range
    Protections: Short circuit/Over load/Over voltage/Over temperature
    Cooling by free air convection
    Can be installed on DIN rail TS-35/7.5 or 15
    LED indicator for power on
    100% full load burn-in test
    2 years warranty 

    2. Specification

    Model
    DR-60-5
    DR-60-12
    DR-60-15
    DR-60-24
    OUTPUT
    DC Voltage 
    5V
    12V
    15V
    24V
    Rated Current 
    6.5A
    4.5A
    4A
    2.5A
    Current Range
    0-6.5A
    0-4.5A
    0-4A
    0-2.5A
    Rated Power 
    32.5W
    54W
    60W
    60W
    Ripple & Noise  (max.) Note.2
    80mVp-p
    120mVp-p
    120mVp-p
    150mVp-p
    Voltage Adj. Range 
    4.75 ~ 5.5V
    11.1 ~ 13.2V
    13.5 ~ 16.5V
    21.6 ~ 26.4V
    Voltage Tolerance Note.3
    ±2%
    ±1%
    ±1%
    ±1%
    LINE REGULATION
    ±1%
    ±1%
    ±1%
    ±1%
    LOAD REGULATION
    ±1%
    ±1%
    ±1%
    ±1%
    Setup, Rise Time 
    100ms, 30ms/230VAC          200ms, 30ms/115VAC at full load
    Hold Up Time
    100ms/230VAC          23ms/115VAC at full load
    INPUT
    Voltage Range
    85~264VAC    124~370VDC
    FREQUENCY RANGE
    47~63Hz
    AC Current
    1.2A/115VAC          0.8A/230VAC
    Efficiency
    76%
    82%
    83%
    84%
    Inrush Current 
    COLD START 18A/115VAC          36A/230VAC
    PROTECTION
    Over Load 
    105%~160% rated output power
    Protection type: Constant current limiting, recovers automatically after fault condition is removed
    Over Voltage 
    5.75 ~ 6.9V
    13.8 ~ 16.2V
    17.25 ~ 20.25V
    27.6 ~ 32.4V
    Protection type : Shut down o/p voltage, re-power on to recover
    ENVIRONMENT
    Working Temp.,
    -20°C~+60°C; (Refer to "Derating Curve")
    WORKING HUMIDITY
    20 ~ 90% RH non-condensing
    Storage Temp., Humidity
    -40°C~+85°C; 10%~95%RH
    Temp. Coefficient
    ±0.03%/°C(0~50°C)
    Vibration
    10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes
    SAFETY
    Withstand Voltage
    I/P-O/P:3KVAC
    Isolation Resistance
    I/P-O/P:100M Ohms / 500VDC / 25°C / 70% RH
    EMC EMISSION
    Compliance to EN55011, EN55022 (CISPR22) Class B, EN61000-3-2,-3
    EMC IMMUNITY
    Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
    OTHERS
    MTBF
    216.2K hrs min.      MIL-HDBK-217F (25°C )
    DIMENSION
    78*93*56mm (W*H*D)

    3. Mechanical Dimension

    4.Block Diagram

    5.Derating Curve

    6.Please Note

    1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
    2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
    3. Tolerance : includes set up tolerance, line regulation and load regulation.
    4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.




  • If you have any enquiry about quotation or cooperation, please feel free to email us at maggie-liu@yqmingwei.com or use the following enquiry form. Our sales representative will contact you within 24 hours. Thank you for your interest in our products.

    E-mail *
      For example : cbh@sscmwl.com
    Message *
    Product
    Your Name *
      For example : Smith Zhang. First name and Last name
    Company
      For example : Yueqing Mingwei Electric Co.,Ltd.
    Country
      For example : China
    Telephone
      For example : 0086-577-62777777 (Country code + City code + Tel numbers)
     

Yueqing Mingwei Electric Co., Ltd.2014 All Rights Reserved    Powered:盛世传媒-温州网站建设-乐清网站建设

Sales Hotline:+86-577-62627101 丨 Wenzhou Yueqing, Zhejiang, China