DR-60
DR series
- Product Overview
- Send Inquiry
-
1.Features
Universal AC input/ full range Protections: Short circuit/Over load/Over voltage/Over temperature Cooling by free air convection Can be installed on DIN rail TS-35/7.5 or 15 LED indicator for power on 100% full load burn-in test 2 years warranty 2. Specification
ModelDR-60-5DR-60-12DR-60-15DR-60-24OUTPUTDC Voltage5V12V15V24VRated Current6.5A4.5A4A2.5ACurrent Range0-6.5A0-4.5A0-4A0-2.5ARated Power32.5W54W60W60WRipple & Noise (max.) Note.280mVp-p120mVp-p120mVp-p150mVp-pVoltage Adj. Range4.75 ~ 5.5V11.1 ~ 13.2V13.5 ~ 16.5V21.6 ~ 26.4VVoltage Tolerance Note.3±2%±1%±1%±1%LINE REGULATION±1%±1%±1%±1%LOAD REGULATION±1%±1%±1%±1%Setup, Rise Time100ms, 30ms/230VAC 200ms, 30ms/115VAC at full loadHold Up Time100ms/230VAC 23ms/115VAC at full loadINPUTVoltage Range85~264VAC 124~370VDCFREQUENCY RANGE47~63HzAC Current1.2A/115VAC 0.8A/230VACEfficiency76%82%83%84%Inrush CurrentCOLD START 18A/115VAC 36A/230VACPROTECTIONOver Load105%~160% rated output powerProtection type: Constant current limiting, recovers automatically after fault condition is removedOver Voltage5.75 ~ 6.9V13.8 ~ 16.2V17.25 ~ 20.25V27.6 ~ 32.4VProtection type : Shut down o/p voltage, re-power on to recoverENVIRONMENTWorking Temp.,-20°C~+60°C; (Refer to "Derating Curve")WORKING HUMIDITY20 ~ 90% RH non-condensingStorage Temp., Humidity-40°C~+85°C; 10%~95%RHTemp. Coefficient±0.03%/°C(0~50°C)Vibration10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axesSAFETYWithstand VoltageI/P-O/P:3KVACIsolation ResistanceI/P-O/P:100M Ohms / 500VDC / 25°C / 70% RHEMC EMISSIONCompliance to EN55011, EN55022 (CISPR22) Class B, EN61000-3-2,-3EMC IMMUNITYCompliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria AOTHERSMTBF216.2K hrs min. MIL-HDBK-217F (25°C )DIMENSION78*93*56mm (W*H*D)3. Mechanical Dimension
4.Block Diagram
5.Derating Curve
6.Please Note
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
-
If you have any enquiry about quotation or cooperation, please feel free to email us at maggie-liu@yqmingwei.com or use the following enquiry form. Our sales representative will contact you within 24 hours. Thank you for your interest in our products.