MDR-60
MDR series
- Product Overview
- Send Inquiry
-
1.Features
•Universal AC input/Full range
•Protections: Short circuit / Overload / Over voltage
•Cooling by free air convection
•Can be installed on DIN rail TS-35/7.5 or 15
•Built in DC OK reply contact
•LED indicator for power on
•No load power consumption<0.75W
•100% full load burn-in test
•2 years warranty2. Specification
MODELMDR-60-5MDR-60-12MDR-60-24MDR-60-48OUTPUTDC VOLTAGE5V12V24V48VRATED CURRENT10A5A2.5A1.25ACURRENT RANGE0 ~ 10A0 ~5A0 -2.5A0-1.25ARATED POWER50W60W60W60WRIPPLE & NOISE (max.) Note.280mVp-p120mVp-p150mVp-p200mVp-pVOLTAGE ADJ. RANGE5 -6V12-15V24 - 30V48 ~ 56VVOLTAGE TOLERANCE Note.3±2.0%±1.0%±1.0%±1.0%LINE REGULATION±1.0%±1.0%±1.0%±1.0%LOAD REGULATION±1.5%±1.0%±1.0%±1.0%SETUP, RISE TIME Note.5500ms, 30ms/230VAC 1000ms, 30ms/115VAC at full loadHOLD UPTIME (Typ.)50ms/230VAC 20ms/115VAC at full loadVOLTAGE RANGE85 ~ 264VAC 120 ~ 370VDCINPUTFREQUENCY RANGE47 ~63HzEFFICIENCY (Typ.)0.780.860.880.87AC CURRENT (Typ.)1.8A/115VAC 1A/230VACINRUSH CURRENT (Typ.)COLD START 30A/115VAC,60A/230VACLEAKAGE CURRENT<1mA/240VACPROTECTIONOVERLOAD105 ~ 150% rated output powerProtection type : Constant current limiting, recovers automatically after fault condition is removedOVER VOLTAGE6.25-7.25V15.6 - 18V31.2-36V57.6 - 64.8VProtection type : Shut down o/p voltage, re-power on to recoverFUNCTIONDC OK ACTIVE SIGNAL (max.)3.75 ~ 6V / 50mA9 ~ 13.5V / 40mA11.5 ~ 16.5V / 40mA18 ~ 27V / 20mAENVIRONMENTWORKING TEMP.-20 ~ +70C (Refer to "Derating Curve")WORKING HUMIDITY20 ~ 90% RH non-condensingSTORAGE TEMP., HUMIDITY-40 ~ +85C, 10 ~ 95% RHTEMP. COEFFICIENT±0.03%/C (0 ~ 50℃)VIBRATIONComponent:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6SAFETY &EMC (Note 4)WITHSTAND VOLTAGEI/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVACISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25C/ 70% RHEMC EMISSIONCompliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3EMC IMMUNITYCompliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024,EN61000-6-1,EN61204-3, light industry level, criteria AOTHERSMTBF299.2K hrs min. MIL-HDBK-217F (25℃)DIMENSION40*90*1000mm (W*H*D)3. Mechanical Dimension
4. Block Diagram
5.DC OK Relay Contact
6.Derating Curve
7.Output Derating VS Input Voltage
8. Please Note
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature. 2.Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1 uf & 47uf parallel capacitor. 3.Tolerance : includes set up tolerance, line regulation and load regulation. 4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5.Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
-
If you have any enquiry about quotation or cooperation, please feel free to email us at maggie-liu@yqmingwei.com or use the following enquiry form. Our sales representative will contact you within 24 hours. Thank you for your interest in our products.